SBH15-M series is a fully sealed three-phase oil-immersed amorphous alloy distribution transformer,rated capacity ranging from 30kVA up to 2500kVA,primary standard voltage 10kV,secondary 0.4kV,strictly compliant with IEC60076&GB/T25446 international&national standards.
Different from conventional silicon steel core transformers,its magnetic core is wound by ultra-thin amorphous alloy ribbon(0.027mm thickness),an isotropic soft magnetic material with disordered atomic structure,high resistivity(3~6 times of silicon steel),ultra-low hysteresis&eddy current loss.It is the top-tier Grade 1 high-efficiency energy-saving distribution transformer widely promoted for global grid upgrade,industrial park,commercial complex,rural power reconstruction and renewable energy power station projects.
Model Code Explanation
S:Three-phase;B:Amorphous alloy core;H:Low-voltage copper foil winding;15:Energy efficiency level;M:Fully sealed structure
2.Core Product Advantages
Ultra-low no-load loss,prominent energy saving
No-load loss cuts down 70%~75%vs S9 silicon steel transformer,65%vs S11 standard,no-load current reduces over 80%,greatly lowers long-term no-load power consumption especially for off-peak idle distribution network,cuts customer annual electricity expense sharply.Amorphous material features tiny magnetizing power,minimal core heat generation and low operating temperature rise.
Fully sealed corrugated tank,maintenance-free design
Adopts all-welded corrugated radiator tank without conservator;vacuum full oil-filling process isolates insulating oil completely from ambient air,avoids oil oxidation,moisture ingress and insulation aging,realizes lifelong maintenance-free under normal service condition.High-quality FKM rubber sealing parts with outstanding anti-aging&oil-resistant performance for long outdoor operation.
Strong short-circuit withstand capability&stable operation
Low-voltage side wound by integral oxygen-free copper foil with uniform ampere-turn distribution;high-voltage enameled copper wire with reinforced insulation;whole body fixed with anti-loose positioning fasteners to avoid coil displacement during transportation or sudden short-circuit impact.Standard Dyn11 connection group suppresses grid harmonic pollution and improves power supply quality.
Green&eco-friendly,wide adaptability
Less power waste reduces fossil fuel consumption&carbon emission,meets global energy-saving&carbon-neutral policy requirements;suitable for high humidity,coastal salt fog,high altitude and remote unattended power distribution sites.Customizable tapping voltage,auxiliary accessories and mounting dimension per client drawing.
3.Main Technical Specifications
Capacity Range:30/50/80/100/160/200/250/315/400/500/630/800/1000/1250/1600/2000/2500kVA
Rated Voltage:HV:6kV/10kV(±2×2.5%);LV:0.4kV(custom voltage available)
Connection Group:Dyn11(Yyn0 optional)
Cooling Mode:ONAN(natural oil circulation,air natural cooling)
Executive Standard:IEC60076,GB/T1094,GB/T25446-2010
Insulation Grade:A/F class optional
4.Standard Optional Accessories
Transformer pressure relief valve,magnetic dial oil level indicator,temperature gauge,off-circuit tap changer,lightning arrester assembly,all matched DIN/IEC standard fittings.
5.Application Fields
Urban&rural power grid renovation,industrial&mining enterprises,shopping malls,high-rise buildings,airport,railway station,photovoltaic/wind power booster station,residential district distribution cabinet,outdoor box-type substation supporting use.
-
How to Distinguish Single‑Phase from Three‑Phase Oil‑Immersed Transformers by Model
2026-06
-
Types of Cooling Methods for Oil-Immersed Transformers
2026-06
-
Differences Between S11, S13, and S15 (SH15) Oil‑Immersed Transformers
2026-06
-
How to Select the Capacity of Oil-Immersed Transformers According to Load
2026-06