SCB14 series 35kV cast resin dry-type transformer is a mature high-efficiency energy-saving power transformer complying with IEC60076,GB/T1094 and national energy efficiency standards,covering rated capacity 50kVA to 5000kVA.It is widely adopted in indoor power distribution projects such as urban substations,high-rise buildings,shopping malls,chemical plants,new energy projects,underground comprehensive pipe corridors and data centers,ideal for fireproof and pollution-free power supply sites.
Core Product Features
1.Optimized Silicon Steel Core,Low Power Loss
High-grade grain-oriented cold-rolled silicon steel sheet with full miter joint cutting process and rational core stacking design.No-load and load losses are much lower than SCB10/SCB11 models,saving long-term running electricity cost and reaching advanced energy efficiency level.
2.Vacuum Epoxy Cast Copper Windings
High/low voltage coils adopt oxygen-free copper wire,integrally cast with high-purity epoxy resin under full vacuum casting.Compact solid coil structure prevents moisture,dust and chemical erosion,features excellent short-circuit withstand capacity and anti-crack performance.Standard connection group:Dyn11/Yyn0,customizable upon customer grid demands.
3.Safe&Eco-friendly,No Fire Hazard
Oil-free design eliminates oil leakage,explosion and fire risks;epoxy resin is flame retardant and self-extinguishing.Can be directly installed indoors without dedicated fire isolation room,cutting construction cost greatly.
4.Dual Cooling Mode&Strong Overload Capacity
Standard cooling:AN(Natural Air Cooling)
Optional AF(Forced Air Cooling with axial fans):allows about 150%temporary overload for peak load condition
Optimized shock absorption structure ensures low operating noise,applicable for residential and downtown environments.
Main Technical Specifications
Primary rated voltage:35kV;Standard secondary voltage:0.4kV,special low voltage customizable
Rated frequency:50Hz;Insulation class:F Class/optional H Class
Full capacity range:
50,100,160,200,250,315,400,500,630,800,1000,1250,1600,2000,2500,3150,4000,5000kVA
Working ambient:-20℃~+40℃,suitable for humid,dusty and mildly corrosive indoor conditions
Optional Attachments
IP20/IP23 protective cabinet,intelligent temperature controller,cooling fans,anti-vibration pads,mobile rolling base,grounding busbar.
Application Scope
Industrial plant power distribution,municipal engineering,photovoltaic&energy storage matching transformation,hospital and commercial complex power supply,petrochemical and mining projects.
-