1.Product Overview
SCB14 series 10kV vacuum cast dry-type transformer is National Class 2 high-efficiency product complying with IEC60076-11,GB1094&latest GB20052-2020/2024 energy efficiency regulation.Rated capacity ranges from 50kVA to 5000kVA;standard primary voltage 10kV,secondary 0.4kV with customizable transformation ratio.
Full oil-free epoxy encapsulated design features flame retardant,explosion-proof and zero pollution,optimized on the basis of SCB13 with further reduced no-load&load loss.Widely used in municipal power grid,commercial buildings,industrial plants,underground subway,photovoltaic power station,chemical and mining projects,the most cost-effective choice for medium-energy-saving power distribution projects.
2.Structure Design
Core Assembly
Adopts high-grade grain-oriented cold-rolled silicon steel sheet with multi-step miter-laminated cutting technique,optimized magnetic circuit to cut no-load loss by 10%~15%vs SCB13.Core surface coated with anti-rust insulated paint,vibration damping structure effectively lowers running noise below industry standard.
HV&LV Windings
10kV High Voltage Coil:High-purity oxygen-free copper wire wrapped with high-temperature resistant insulation,integral vacuum epoxy casting,partial discharge controlled below≤5pC,outstanding moisture-proof&anti-aging property.
Low Voltage Coil:Small capacity:copper wire winding;large capacity:full copper foil winding,uniform current distribution,low extra eddy loss and strong short-circuit withstand capacity.
Epoxy resin is F1 self-extinguishing grade,no molten drop under open fire;standard F-class insulation(155℃),optional H-class(180℃)for high-temperature harsh environment.
Auxiliary Accessories
Built-in PT100 platinum thermal sensors matched with intelligent temperature controller,realizing automatic cooling fan startup,over-temperature alarm and overheat trip protection.Two cooling options:AN natural air cooling(standard),AF forced air cooling;under AF mode,the transformer supports 20%temporary overload operation.Optional IP20/IP23 metal protective cabinet for anti-touch and dust prevention.
3.Core Advantages
Cost-effective Class 2 Energy Saving:No-load loss down 10%~15%,load loss down 8%~12%compared with SCB13,much lower energy consumption than SCB10/SCB11;balances energy-saving performance and procurement cost,ideal for medium-load projects with high cost-performance demand.
Excellent Safety&Eco-friendly:Oil-free construction eliminates leakage,fire and explosion risks;no waste oil discharge,pollution-free,can be directly installed indoors without special fireproof oil pit.
Strong Environmental Adaptability:Stable operation under high humidity,dust,coastal salt fog and mild corrosive atmosphere;applicable altitude≤1000m,ambient temperature-25℃~+40℃,C1 climate grade per IEC.
Low Noise&Minimal Maintenance:Optimized assembling&damping design,running noise 10~15dB lower than standard JB/T10088 requirement;oil-free design removes regular oil replacement and filtration work,only annual simple dust cleaning needed to cut O&M cost.
High Mechanical Stability:Integral cast winding improves mechanical strength against short-circuit impulse,long service life over 30 years under rated working condition.
4.Main Technical Specifications
Rated Capacity:50,80,100,160,200,250,315,400,500,630,800,1000,1250,1600,2000,2500,3150,4000,5000kVA
Primary Voltage:10±2×2.5%kV/±5%tap changer customizable
Secondary Voltage:0.4kV,special non-standard voltage available
Rated Frequency:50Hz,60Hz customized for overseas markets
Insulation Grade:F(standard)/H(optional)
Vector Group:Dyn11(default),Yyn0 optional
Protection Level:IP00(bare transformer),IP20/IP23(with enclosure)
Standard Impedance Voltage:6%,adjustable on customer request
5.Application Fields
Urban power grid upgrading,shopping mall&high-rise residential power distribution,hospital,subway tunnel,industrial workshop,distributed PV station,chemical park,mine power room,data center auxiliary power supply.
-